- Breakers, Four Poles MCCB, MCB & MCCB
Schneider Electric® EasyPact MCCB EZC100N 4P 15kA 400/415V
Specification Details
Poles: 4P (3 phases + neutral)
Rated Current (In): Typically up to 100 A (model-dependent)
Operational Voltage (Ue): Up to 550 V AC / 250 V DC
Rated Insulation Voltage (Ui): 690 V AC
Impulse Withstand (Uimp): 6 kV AC
Interrupt Capacity (Icu):15 kA @ 415 V AC; 18 kA @ 380–400 V AC; 25 kA @ 110–240 V AC
Service Breaking (Ics): Up to ~12.5 kA depending on voltage level
Usage Category: Category A
Trip Technology: Fixed Thermal-Magnetic (TM-D)
Mechanical Durability: ~8,500 operations
Electrical Durability: ~1,500 cycles at full load
Control Type: Front-toggle with positive contact indication
Dimensions: ~130 × 100 × 60 mm
Mounting: Fixed backplate
Protection Ratings: IP20 / IK07
Operating Temperature: -25 °C to +70 °C
Standards: IEC/EN 60947‑1 & ‑2, UL508, marine-compatibleSKU: n/a - Breakers, MCB & MCCB, Three Poles MCCB
Schneider Electric® EasyPact MCCB EZC250N 3P 25kA 400/415V
Specification Details
Poles: 3 Pole (3P)
Rated Current (In): Up to 250 A (model-dependent)
Rated Operational Voltage (Ue): 550 V AC or 250 V DC; Standard is 400–415 V AC
Insulation Voltage (Ui): 690 V AC
Impulse Withstand (Uimp): 6 kV AC
Breaking Capacity (Icu): 25 kA @ 400–415 V; up to 50 kA at lower voltages
Service Breaking Capacity (Ics): 12.5 kA at 400–415 V; 25 kA at 220–240 V
Trip Unit: Fixed thermal-magnetic (TM‑D)
Utilization Category: Category A
Mechanical Durability: ~10,000 cycles
Electrical Durability: ~5,000 cycles at full load
Dimensions (H × W × D): ~165 × 105 × 60 mm
Mounting: Fixed backplate (front connections)
Protection Rating: IP20, IK07
Operating Temperature Range: –25 °C to +70 °CSKU: n/a - Breakers, Four Poles MCCB, MCB & MCCB
Schneider Electric® EasyPact MCCB EZC250N 4P 25kA 400/415V
Brand Schneider Electric Series EasyPact EZC Model EZC250N Poles 4P (3 Phase + Neutral) Rated Current (In) Up to 250A (selectable range) Rated Operational Voltage (Ue) 400–415V AC Interrupting Capacity (Icu) 25kA @ 400/415V Insulation Voltage (Ui) 690V AC Trip Unit Thermal-Magnetic (Fixed) Standard Compliance IEC 60947-2 Mounting Fixed, Panel Mount Protection Class IP20 Application Distribution boards, panel protection SKU: n/a - Breakers, Four Poles MCCB, MCB & MCCB, Three Poles MCCB
Schneider MCCB CVS250B with Adjustable Thermal Magnetic Trip
Breakers, Four Poles MCCB, MCB & MCCB, Three Poles MCCBSchneider MCCB CVS250B with Adjustable Thermal Magnetic Trip
Specification Details
Poles: 3P / 4P (3 phases + neutral)
Rated Current (In): Up to 630A (adjustable)
Breaking Capacity (Icu): 25 kA @ 380–415 V; 40 kA @ 220–240 V
Service Breaking (Ics): 15 kA @ 440 V
Trip Unit: TM-D Thermal‑Magnetic (Adjustable Ir, fixed Ii)
Utilization Category: A (standard load switching)
Mechanical Durability: ~30,000 cycles
Electrical Durability: ~12,000 cycles @ 415 V In
Impulse Withstand Voltage: 8 kV (Ui/Uimp)
Protection Rating: IP40 (standard)
Ambient Temperature: –25 °C to +70 °C operational, –50 °C to +85 °C storage
Standards Compliance: IEC/EN 60947‑2, GOST, RoHS, REACH, WEEESKU: n/a - Breakers, Relays
Schneider Zelio RM22TR33 3 Phase Voltage Control Relay
Technical Specifications
Product Type: 3-phase voltage control relay
Monitored Parameters: Phase sequence, overvoltage, undervoltage, and phase failure detection
Rated Supply Voltage: 380-480 V AC
Supply Voltage Limits: 304-576 V AC
Output Contacts: 2 Changeover (C/O) contacts
Nominal Output Current: 8A
Switching Capacity: 2000 VA
Time Delay: Adjustable from 0.1 to 30 seconds
Mounting Support: 35mm DIN rail
Housing Material: Self-extinguishing plastic
Operating Temperature: -20°C to +60°C
Degree of Protection:
IP20 (terminals)
IP40 (housing)
IP50 (front panel)
Dimensions (W x H x D): 22.5 x 90 x 73 mm
Standards Compliance: IEC 60664-1, UL 508SKU: n/a